The MovinCool Classic Plus 14 portable AC has all the benefits of our proven Classic Series, PLUS new features designed to increase performance and control. The Classic Plus is the most versatile of our portable AC units. It is instantly ready to provide cool air in the hottest environments such as production lines, outdoor events, manufacturing processes, injection molding, metal forming and much more.
The Classic Plus features a programmable, programmable temperature controller allowing the user to “set” the desired temperature. At 13,200 Btu/hr of cooling, the Classic Plus 14 provides the maximum capacity possible operating on standard 115V, 15amps power. By cooling only the area that needs it, the Classic Plus 14 portable A/C saves you money while protecting people and equipment and speeding up processes. Self-contained and portable, the Classic Plus 14 requires little or no installation – simply roll it in, plug it in and turn it on.
Electronic Features
|
Control Panel
|
Programmable
|
Thermostat Control |
Electronic |
Cooling Capacity
|
Rating Conditions: 95F at 60% RH
|
13,200 Btu/h
|
Electrical Characteristics
|
Voltage Requirement
|
1 Phase, 115V
|
Total Power Consumption |
1.3 kW |
Current Consumption |
11.9 amps |
Recommended Fuse Size |
15 amps |
NEMA Plug Configuration |
5 – 15 |
Min. Max. Voltage |
105 – 125 |
Fans
|
Motor Output
|
0.24/0.19 kW
|
Evaporator
|
Fan Type
|
Centrifugal
|
Max Air Flow high/low |
440/380 CFM |
Max External Static Pressure |
0.31 IWG |
Condenser
|
Fan Type
|
Centrifugal
|
Max Air Flow high/low |
880/760 CFM |
Max External Static Pressure |
0.19 IWG |
Compressor
|
Type
|
Hermetic Rotary
|
Output |
0.9 kW |
Refrigerant
|
R-410A
|
1.65 lb
|
Dimensions
|
W x D x H
|
19 x 26 x 41 in
|
Net Weight/Shipping Weight
|
|
166/197 lb
|
Power Cord
|
Gauge
|
14 AWG (3 – core)
|
Length |
10 ft |
Condensate Tank Capacity
|
|
5 gal
|
Operating Conditions
|
Min. Max. (@ 50% RH)
|
70° – 113°F
|
Max. Duct Length
|
Per Cold Duct Hose
|
30 ft
|
Hot Duct Hose |
60 ft |
Max. Sound Level
|
With Condenser – Duct high/low
|
57/55 dB(A)
|
Without Condenser – Duct high/low |
60/58 dB(A) |